67
1
O PER AT I O N , M A I N T EN A N C E , A N D I N S TA L L AT I O N G U I D E
—
5.4 Using Ekip Signalling 2K-_ -module
The Ekip Signalling 2K-_ is a signalling
accessory module. It is suitable for all
ZTS(D) 1600-3000 A and ZTSCT
100-3000 A, 208-480 Vac automatic
transfer switches. The module has:
• Two digital inputs, and two contacts for
output signals.
• A power status LED, and four signalling
LEDs (one LED for every input/output).
Notice
On each ATS, a maximum of three Ekip Signal-
ling 2K modules can be installed: one 2K-1, one
2K-2, and one 2K-3. These modules differ by
their name and label, and have distinct wiring,
but they are identical in terms of their charac-
teristics and manner of installation.
5.4.1 Electrical characteristics of
Ekip Signalling 2K-_ -module
The following table lists the electrical
characteristics of the module:
Component
Characteristics
Output
contacts
Maximum switching voltage*:
150 V DC / 250 V AC
Breaking power*: 2 A @ 30 V DC,
0.8 A @ 50 V DC, 0.2 A @ 150 V
DC, 4 A @ 250 V AC
Dielectric strength between
each contact and coil: 1000 V AC
(1 minute @ 50 Hz)
Dielectric strength between
open contacts: 1000 V AC (1
minute @ 50 Hz)
Input contacts
5 [email protected] mA
Do not connect to any power
supply
*Data relating to a resistive load
—
Table 5.3 Electrical characteristics of
Ekip Signalling 2K-_ -module
5.4.2 Access from the display /
Ekip Signalling 2K-_ -module
With modules energized, and Local Bus
enabled, the presence of the modules on
the module slot activates additional
menus on the display:
• In order to configure the inputs and out-
put contacts.
• To display information on the modules
and the state of inputs and outputs.
The following table illustrates the path for
accessing the configuration parameters
of the module from the display:
—
Fig. 5.8 Ekip Signalling 2K -module
Summary of Contents for Zenith ZTS T Series
Page 2: ...2 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 6: ...6 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 10: ...10 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 36: ...36 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 44: ...44 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 106: ...106 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 108: ...108 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 122: ...2 122 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 126: ...2 126 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 129: ...129 1 OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...