Settings (*Default)
Description
Modules (Optional modules)
Ekip Signalling 2K-1 / -2 / -3
I 11/12, I 21/22, I 31/32
Function No Function*
Input disabled
Emergency Stop
Transfers to O position in delayed transition and closed
transition I-O-II type switches. Disables automatic
control mode in delayed, closed, and open transition
types.
Remote Test on Load
Start/stop test on load sequence in rising (NO) or falling
(NC) edge of the input signal.
Remote Test off Load Start/stop test off load sequence in rising (NO) or falling
(NC) edge of the input signal.
Inhibit ATS
Prevent switch control operations, configuration, test
sequences and generator start in case of priority source
failure.
Manual Retransfer
Disables automatic transfer back to priority source.
Source Priority S1
Sets priority for source 1 in transformer-transformer
application.
Source Priority S2
Sets priority for source 2 in transformer-transformer
application.
Inhibit Transfer
Disables automatic transfer from priority source to non-
priority source.
Bypass Running Time
Delays
Bypass any currently running time delay.
Remote Control to S1
Transfer to S1 when active. Overridden by activated
'Remote Control to OFF' signal.
Remote Control to OFF Transfer to position O when active.
Remote Control to S2
Transfer to S2 when active. Overridden by activated
'Remote Control to OFF' or 'Remote Control to S1'
signals.
Reset Alarm
Reset any active switch control alarms (open I failure,
close I failure, open II failure, close II failure).
Manual-Auto Mode
Toggle automatic/HMI control mode, input is active only
in rising/falling edge according to contact type.
Contact
Type
NC
Active open
NO*
Active closed
Continued on the next page
Summary of Contents for Zenith ZTS T Series
Page 2: ...2 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 6: ...6 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 10: ...10 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 36: ...36 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 44: ...44 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 106: ...106 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 108: ...108 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 122: ...2 122 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 126: ...2 126 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 129: ...129 1 OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...