2.5.2.2 SOURCE 2 Priority
(No Generator)
The switching sequence can be
summarized in the following steps:
1
Activate test on load (HMI or digital
input)
2
Pre-transfer S2 to S1 delay
3
Check source synchronization
4
Close SOURCE 1 contacts
5
Open SOURCE 2 contacts, start ETT
timer (parallel mode)
6
Post-transfer S2 to S1 delay
The re-transfer sequence can be summa-
rized in the following steps:
1
Cancel test on load (HMI or digital
input)
2
SOURCE 2 availability timer
3
Pre-transfer S1 to S2 delay
4
Check source synchronization
5
Close SOURCE 2 contacts
6
Open SOURCE 1 contacts, start ETT
timer (parallel mode)
7
Post-transfer S1 to S2 delay
Summary of Contents for Zenith ZTS T Series
Page 2: ...2 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 6: ...6 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 10: ...10 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 36: ...36 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 44: ...44 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 106: ...106 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 108: ...108 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 122: ...2 122 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 126: ...2 126 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 129: ...129 1 OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...