O PER AT I O N , M A I N T EN A N C E , A N D I N S TA L L AT I O N G U I D E
5.5.3.3 Access from the display /
Ekip Com DeviceNet –module
With modules connected and energized,
the presence of the modules on the mod-
ule slot activates additional menus on
the display.
The following table illustrates the path for
accessing the configuration parameters
of the modules from the display:
Settings (*Default value)
Description
:
Modules (Optional modules)
Ekip Com DeviceNet
MAC address
1-63, default 63*
Address to be assigned to the
modules. IMPORTANT: devices
connected to the same network
must have different addresses
Baudrate
125 kbit/s, 250 kbit/s*, 500 kbit/s
Data transmission speed
:
—
Table 5.13 The path for accessing the configuration parameters of the Ekip Com DeviceNet -module from the display
The following table illustrates the path
from the display for accessing informa-
tion on the module:
About
Description
:
Modules (Optional modules)
Ekip Com DeviceNet
SN
Serial number
Version
Software version
:
—
Table 5.14 Information of Ekip Com
DeviceNet -module in HMI
Summary of Contents for Zenith ZTS T Series
Page 2: ...2 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 6: ...6 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 10: ...10 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 36: ...36 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 44: ...44 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 106: ...106 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 108: ...108 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 122: ...2 122 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 126: ...2 126 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 129: ...129 1 OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...