ABB | SACE Tmax XT
External electronic accessories | 7 - Ekip Com EtherNet/IP TM
157 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Information in menu
The following information will be available in the
About
-
Modules
menu if Ekip Touch has detected the module
correctly:
Information
Description
SN and version
Identifier and SW version of the module
IP address
Address of the module, assigned to the module by a DHCP server at the time of
connection to the network in the case of configuration with a dynamic IP, or can be
set via the menu in the event of a static IP.
NOTE
:
without a DHCP server, the module automatically adopts a random IP
address within the 169.254.xxx.xxx
range
Network Mask
Subnet mask; identifies the method for recognizing the subnet to which the modules
belong and enables modules to be searched for within a defined set of recipients.
Gateway address
IP address of the node to which the module is connected, in the presence of several
subnets
MAC address
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to
ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device
Remote configurations
Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter
Description
Default
Enable IEEE
1558
Allows the IEEE 1588 protocol for distribution of the clock and
synchronization signal to be enabled
(1)
.
OFF
IEEE 1558
Master
Enables the module to be set up as a master in the the network
segment to which it belongs (synchronization clock).
OFF
IEEE 1558 Delay
mechanism
Allows the data exchange mode between module and master, either
Peer-to-Peer or End-to-End, to be selected.
End-to-End
Enable client
SNTP
Allows the SNTP protocol for distribution of the clock and
synchronization signal to be enabled
(1)
OFF
ANTP Server
address
Allows the network server that supplies the SNTP to be set.
0.0.0.0
Time zone
Defines the time zone to be used for synchronism
+00:00
Daylight Saving
Time
Used to select whether daylight saving time is present (ON) or not
(OFF) in the country to which the synchronization time refers
OFF
(1)
Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
Remote information
Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information
Description
HW and Boot version
General module information
Flash CRC status and result
Information about the correctness of the SW in the module
Ekip Link status
Signals Ethernet cable connection errors
SNTP Server Error
Error in communication with SNTP server
SNTP Server Synchronization
State of synchronism with SNTP server
IEEE 1558 status
Valid with Master IEEE 1588=
ON
, notifies the presence (Slave or PTP
Master Active) or absence (PTP Master but Passive) of a higher level
master