ABB | SACE Tmax XT
External electronic accessories | 8 - Ekip Com IEC 61850
159 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Models
Two different modules compatible with the IEC 61850 protocol are available:
Ekip Com IEC 61850
and
Ekip
Com IEC 61850 Redundant
.
The modules are identical in terms of characteristics and installation methods, except for: display menus,
cabling and addresses for system communication, which are specific for each module.
NOTE:
if different indications are not given, the information in the next chapter is valid for
both models
The two modules can be connected at the same time to Ekip Touch so as to expand the potential of the unit
(e.g. for applications where high grid reliability is required).
IMPORTANT: each Ekip Touch can be fitted with only one module per type. The
configuration with two modules of the same model is not allowed (example: two
Ekip Com IEC 61850 Redundant)
Connections
The module must be assembled in the first vacant slot of the terminal box after
Ekip Supply
, either on the
circuit-breaker (fixed version) or on the fixed part (withdrawable version).
For references about the connection and terminals, please consult document
of the Class 6 S/FTP type (Class 6 with double screening S/FTP) must be used for the communication bus.
To connect the module to Ekip Touch, please consult document
.
Power supply
Ekip Com IEC 61850
is supplied directly by the
Ekip Supply
module to which it is connected.
NOTE:
communication between Ekip Touch and the module is interrupted in the absence of
auxiliary power supply
Interface
the module has three signaling leds:
1
2
Figure 49
LEDs
Description
Power
Signals the on status and correct communication with Ekip Touch:
• off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module on
and communication with Trip unit present.
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per
second): module on and communication with Trip unit absent.
Link (
1
)
Indicates the communication state:
• off: incorrect connection, signal absent.
• on steady: connection correct
Activity (
2
)
Indicates the communication state:
• off: no activity on line
• flashing: activity on line present (receiving and/or transmitting)