ABB | SACE Tmax XT
Ekip Touch - Measurements | 5 - Network Analyzer
123 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Spikes
The
Spikes
counter should be understood as increase of the RMS value of the line-to-line voltage above the
set
V Spike Threshold
threshold for less than 40 ms (short time voltage spike).
The counter is available in the two submenus
Counters
-
Day
-
1 and Counters
-
Cumulative
(previous day or
cumulative)
NOTE:
Since the counter is based on the RMS value calculation, two rapid voltage spikes of
equal duration may be evaluated differently, depending on their amplitude:
t
t
Increase detected
Increase not detected
Additional List
Counters
(Interruptions)
Description
Last time stamp
Date and time of last recording of the
Spikes
counter
Last value
Value of last swell above
Spikes
[V] threshold
Last duration
Duration of last swell above
Spikes
[ms] threshold
Actual number of S.
Spikes
count for the current day
Actual [day -2 ... day -7]
number of S.
Spikes
count of the last seven days of activity, calculated using the internal
clock of the unit
Sags
Certain counters relating to sags are available in the
Counters
-
Day
-
1 and Counters
-
Cumulative
submenus:
Counters
(Interruptions)
Description
Sags Short
Counts the number of times that any line-to-line voltage falls below the
V sag
Th Short
threshold for longer than
V sag dur Short
Sags Middle
Counts the number of times that any line-to-line voltage falls below the
V sag
Th Middle
threshold for longer than
V sag dur Middle
Sags Long
Counts the number of times that any line-to-line voltage falls below the
V sag
Th Long
threshold for longer than
V sag dur Long
The count refers to the reference menu interval (previous day or cumulative)
NOTE:
since an event may fall under more than one category, only the counter of the main
type (Long > Middle > Short) is increased
Additional List
Counters
(Interruptions)
Description
Last time stamp
Date and time of last recording of the
Sags Short
counter
Sags Middle
Value of last sag below the
Sags Short
[V] threshold
Sags Long
Duration of last sag below the
Sags Short
[ms] threshold
Actual number of S.
Sags Short
count for the current day
Actual [day -2 ... day -7]
number of S.
Sags Short
count of the last seven days of activity, calculated using the internal
clock of the unit
Continued on the next page