ABB | SACE Tmax XT
146 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
External electronic accessories | 4 - Ekip Com DeviceNet TM
4 - Ekip Com DeviceNet
TM
Ekip Com DeviceNet
TM
is a communication accessory which allows Ekip Touch to be integrated into a CAN
network with DeviceNet
TM
communication protocol, with remote supervision and monitoring functions.
The module is configured as a Slave and remotely, you can:
• read Ekip Touch measurements and information
• manage certain controls, including opening and closing the actuator (MOE-E)
• access information and parameters not available on the display
• If connected to a withdrawable version of the circuit-breaker, the allows the racked-in/racked-out status
to be detected
NOTE:
the remote open and close commands of the circuit-breaker can only be executed if
Ekip Touch is in the Remote configuration
and the circuit-breaker is equipped with the
Ekip Com Actuator module (page
)
The System Interface document is available for mapping the module in its communication network. All the
required communication and command details are listed in the document (page 139).
Models
Two different modules compatible with the DeviceNet
TM
protocol are available:
Ekip Com DeviceNet
TM
and
Ekip Com DeviceNet
TM
Redundant
.
The modules are identical in terms of characteristics and installation methods, except for: display menus,
cabling and addresses for system communication, which are specific for each module.
NOTE:
if different indications are not given, the information in the next chapter is valid for
both models
The two modules can be connected at the same time to Ekip Touch so as to expand the potential of the unit
(e.g. for applications where high grid reliability is required).
IMPORTANT: each Ekip Touch can be fitted with only one module per type. The
configuration with two modules of the same model is not allowed (example: two
Ekip Com DeviceNetTM Redundant)
Connections
The module must be assembled in the first vacant slot of the terminal box after
Ekip Supply
, either on the
circuit-breaker (fixed version) or on the fixed part (withdrawable version).
For references about the connection and terminals, please consult document
Belden 3084A type cables or equivalent for the external cabling.
To connect the module to
Ekip Supply
and
Ekip Cartridge
, please consult documentTo connect the module
to Ekip Touch, please consult document
.
Power supply
Ekip Com DeviceNet
TM
is supplied directly by the
Ekip Supply
module to which it is connected.
To function correctly, the DeviceNet
TM
bus must be supplied on terminals V+ and V- with a signal of over 12 VDC.
NOTE:
• the ABB PLC with DeviceNet (CM575-DN) communication module provides V+ V- supply
• communication between Ekip Touch and the module is interrupted in the absence of power
supplies from Ekip Supply and on the supply terminals of the bus