16.5 Table showing list of events
16.5.1
"Standard" events for PR120/K and for PR021/K selectable from the relay
Event no.
Description
0.
None
(none enabled)
1.
L prealarm
(L protection prealarm)
2.
L timing
(L protection timing)
3.
S timing
(S protection timing)
4.
L trip
(L protection trip)
5.
S trip
(S protection trip)
6.
I trip
(I protection trip)
7.
G trip
(G protection trip)
8.
Any trip
(tripping of any protection)
16.5.2 "Standard" events for the Data Logger function, selectable from the relay
Event no.
Description
0.
None
(free running)
1.
Any alarm
(any alarm)
2.
L timing
(L protection timing)
3.
Any trip
(tripping of any protection)
16.5.3 Examples of "Custom" events for the Data Logger function, for PR120/K and PR021/K
No. (decimal)
Event
Notes
PR122
PR123
1920
G timing
x
x
2894
L1 or L2 or L3 sensor error or Trip Coil error
x
x
2688
LC1 alarm
x
x
2049
G alarm
x
x
2306
UV timing
x
x
4124
UV or OV or RV tripped
x
x
33672
CB connected and springs charged
x
x
1793
Harmonic distortion > 2.1
x
x
You can combine the status bits with "and" / "or" logical functions within the same group of events (byte). For more detailed information, refer to
the Modbus Interface document.
16.5.4 Combining the devices needed to customize settings
The "custom" events can be selected using a remote control system, SD-Pocket, or SD-TestBus.
The devices you need to enable you to do so can be selected from among the following:
1) PR122/P + BT030 + SD-Pocket
2) PR122/P + PR120/D-M + SD-Testbus or remote system
3) PR122/P + PR120/D-BT + SD-Pocket
4) PR122/P + PR010/T
5) PR123/P + BT030 + SD-Pocket
6) PR123/P + PR120/D-M + SD-Testbus or remote system
7) PR123/P + PR120/D-BT + SD- Pocket
8) PR123/P + PR010/T