L2234
Emax
49/158
Model
Scale
Page No.
Doc. No.
Apparatus
1SDH000460R0002
L2778
Protection
Disabling
Disabling of
TRIP only
Zone selectivity
Start-up threshold
Thermal memory
Trip Threshold
Trip time
tolerance
(2)
Trip Time
Trip
threshold
tolerance
( 2 )
13.2.9.12 Summary table of the protection function settings for the PR122/P
(1)
The minimum value of this trip is 1s regardless of the type of curve set (self-
protection).
(2)
These tolerances are based on the following assumptions:
- self-supplied relay at full power (without start-up)
- presence of auxiliary power supply
- two-phase or three-phase power supply
- preset trip time
≥
100 ms.
(3)
no-trip time
(4)
the protection G is disabled for current values greater than 4In, where I4 < 0.5 In,
greater than 6 In, where 0.5 In
≤
I4 < 0.8 In and greater than 8 In where I4
≥
0.8 In.
(5)
Max trip time
For all cases not covered by the above hypotheses, the following tolerance values
apply:
Protections
Trip threshold
Trip time
L
Release between 1.05 and 1.25 x I1
± 20%
S
± 10%
± 20%
I
± 15%
≤
60ms
G
± 10%
± 20%
Others
± 20%
L
(t=k/i
2
) curve
0.4xIn
≤
I
1
≤
1xIn
3 s
≤
t
1
≤
144 s
(1)
, step 3s
Release between
± 10%, I
g
≤
6In
IEC 60255-3
step 0.01xIn
t1@ 3I
1
1.05 and1.2 xI1
± 20%, I
g
>
6In
S
0.6 xIn
≤
I
2
≤
10xIn
0.05 s
≤
t
2
≤
0.8 s, step 0.01s
± 7%,I
g
≤
6 In
The best of the two data
(t=k)
step 0.1xIn
0.10 s
≤
t
2 start-up
≤
30 s, step 0.01s
± 10%,I
g
>
6 In
± 10% or 40 ms
0.6 xIn
≤
I
2 start-up
≤
10xIn 0.04 s
≤
t
2 sel
≤
0.20 s, step 0.01s
step 0.1xIn
S
0.6xIn
≤
I
2
≤
10xIn
0.05 s
≤
t
2
≤
0.8 s,
± 7%,I
g
≤
6 In
± 15%, I
g
≤
6In
(t=k/i
2
)
step 0.1xIn
step 0.01s at 10xIn
± 10%,I
g
>
6 In
± 20%, I
g
>
6In
I
1,5xIn
≤
I
3
≤
15xIn
≤
30ms
(t=k)
step 0.1xIn
0.10 s
≤
t
2 start-up
≤
30 s, step 0.01s
± 10%
where I>I4
MCR
6.0xIn
≤
I
5
≤
15xIn
≤
30ms
(3)
± 10%
(t=k)
step 0.1xIn
G
(4)
0.20xIn
≤
I
4
≤
1xIn
0.1 s
≤
t
4
≤
1 s, step 0.05s
The best of the two data
(t=k)
step 0.02xIn
0.1 s
≤
t
4 start-up
≤
30s, step 0.01s
± 7%
± 10% or 40 ms
0.04 s
≤
t
4 sel
≤
0.2 s, step 0.01s
where I>I4
G
(4)
0.20xIn
≤
I
4
≤
1xIn
0.1 s
≤
t
4
≤
1 s, step 0.05s
± 7%
± 15%
(t=k/i
2
)
step 0.02xIn
0.10 s
≤
t
2 start-up
≤
30s, step 0.01s
@I
g
>4In
Gext
0.20xIn
≤
I
4
≤
1xIn
0.1 s
≤
t
4
≤
1s, step 0.05s
The best of the two data
(t=k)
step 0.02xIn
0.1 s
≤
t
4 start-up
≤
1.5s, step 0.01s
± 7%
± 10% or 40 ms
0.20xIn
≤
I
4
≤
1xIn
0.04 s
≤
t
4 sel
≤
0.2s, step 0.01s
step 0.02xIn
where I>I4
Gext
0.20xIn
≤
I
4
≤
1xIn
0.1s
≤
t
4
≤
1s, step 0.05s
± 7%
± 15%
(t=k/i
2
)
step 0.02xIn
@I
g
>4In
Rc
Idn =3.0-5.0-7.0-10-20 0.06-0.10-0.20-0.30-0.40-0.50
(5)
(Idn)
-30A 0.80s
(3)
0 ÷ 20% [email protected]
(5)
U
2%
≤
I
6
≤
90% %Unb.
0.5s
≤
t
6
≤
60 s, step 0.5s
± 10%
The best of the two data
(t=k)
step 1%
± 10% or 40 ms
OT
Fixed, defined by
Instantaneous
± 5°C
- - -
(temp=k)
SACE
Iinst
Automatic, defined
Instantaneous
by SACE
LC1/LC2 loads
50%
÷
100% step 0.05xI
1
control
Warning Iw
0,3
÷
10I
n
step 0,05xI
n
± 10%
10
÷
40 ms