2105552MNAE | RMC-100 |
69
Figure 4-30: Digital input and output configuration
3.
Select the Type from the drop-down list (Digital Input is the default).
4.
Configure each Digital I/O:
•
Digital input mode: select the low and high threshold voltage.
•
Digital output mode: select the current value and the initial value.
5.
Click
Send
.
4.9.5
Pulse input configuration
Each pulse input has a debounce filter. Without debounce, the PI operates at a frequency range of 0
to 20 kHz. With debounce the frequency range is 1 to 550 Hz.
To configure the pulse input:
1.
Click
I/O System
on the navigation tree.
2.
Click
Pulse Inputs
Figure 4-31: Pulse input configuration
3.
Click the Value field for PI 1 or PI 2 under Debounce and select
On
from the drop-down list.