| RMC-100| 2105552MNAE
Figure 7-3: Calibration request to take application out of hold mode
6.
Click
OK
to take each application out of hold. The calibration dialog stops displaying after the
last application is out of hold.
7.
Click the
Onboard I/O
folder on the navigation tree to expand it. Then click Analog Inputs.
The Analog Input 1-tab displays (
Figure 7-4: Analog Input 1 default calibration values
8.
Click another Analog Input tab, if necessary, to calibrate.
9.
Select either
3 Point
or
5 Point
calibration from the Calibration drop-down list (
10.
Verify that only the Zero Input and Low Cal Point buttons are enabled and highlighted. The
system enables the buttons in the required order for the calibration.