150
| RMC-100| 2105552MNAE
Figure 7-34: Low range value verification
3.
Adjust the calibrator to apply the high (100%) value of the signal range.
4.
Wait for the value in Current Value to stabilize (
5.
Verify that Current Value displays a value equal or close to the target range high (100%) value