2105552MNAE | RMC-100 |
145
20.
Click
100% Cal Point
. The Enter 100% Calibration Value box displays (
21.
Type the range high value into the entry field. (1500.000 in this example).
Figure 7-28: High (100%) Calibration value entry field
22.
Adjust the calibrator to apply the high value (100%) of the signal range. For example, if the
signal range of the external device is 4 to 20 mA, apply 20 mA.
23.
Observe the value in the Current Reading field (
). The expected voltage value for a
20 mA input is approximately 5 Vdc (0.02 * 250 = 5 Vdc).