136
| RMC-100| 2105552MNAE
Figure 7-15: Calibration complete message
26.
Click
OK
. Verify that the Entry and Reading values update, and that the Current Value field
displays the calibrated value based on the defined range (
IMPORTANT NOTE:
After calibration is complete the Current Value field displays range values, not
voltage values.
Figure 7-16: Calibrated AI 1 example (voltage mode)
27.
Remain in the calibration screen and keep the calibrator connected to the AI.
28.
To verify the calibration, proceed to section
, Verify analog input calibration.