2105552MNAE | RMC-100 |
135
Figure 7-13: High calibration value reading
22.
Adjust the calibrator to apply the 50% value of the external device signal range. For example, if
the signal range of the external device is 1-5 Vdc, apply 3 Vdc.
23.
Click
50% Cal Point
. The Enter 50% Calibration Value dialog box displays with the target mid-
value automatically calculated. In
, the box displays 750.000. This is the mid-value
of 1500.
24.
Wait for the value in the Current Reading field to stabilize. This value should match or be close
to the signal value from the calibrator (~ 3 Vdc).
Figure 7-14: User-defined mid calibration value
25.
Click
OK
. The Calibration Complete message displays (