Displays up to 14 binary input modules with 16 binary values per module.
11.3.1.2
Signal matrix for binary input (SMBI)
Test/Binary Input Values/SMT Binary Inputs/Instance
Displays up to 30 instances of SMT binary inputs with 10 inputs per instance.
11.4
View binary output values
11.4.1
Overview
Binary output values show the status of each individual output in the Binary output
module (BOM). If the signal matrix tool is used binary outputs are depicted as virtual
outputs. Note, that only modules installed in the IED are shown in the HMI.
11.4.1.1
Binary Output Module (BOM)
Measurements/Binary Output Values/Binary Output Modules/BOM
Displays up to 14 binary output modules (BOM). The status and name of each of the
24 binary outputs that each module has are displayed here. The name of each output
is user defined string. The names of binary outputs are changed in the setting menu.
11.4.1.2
Signal matrix for binary outputs (SMBO)
Measurements/Binary Output Values/SMT Binary Outputs/Instance
Displays up to 30 sets of binary output values. Each set or
instance
of binary outputs
displays the status of 10 individual binary outputs.
11.5
Function test modes
11.5.1
Differential protection
Test/Function test modes/Differential protection
Test of the low and high impedance restricted earth fault protection as well as
transformer differential protection testing.
11.5.2
Distance protection
Test/Function test mode/Distance protection
Section 11
Test the IED
RET 670
Operator's manual
1MRK504049-UEN rev. D
57