should be zero, the positive sequence current should be equal to the current of each
phase with the same phase angle (relative to GPS) as the L1 phase signal and the
negative sequence current should be zero.
6.5.5
Voltage sequence component
Measurements/Monitoring/Voltage Sequence Components (MSQI)
The Voltage sequence component displays the positive (U1), negative (U2) and zero
(U0) sequence components in the system, and includes the magnitude and phase angle
of each component. Three sets of values are shown. This data indicates how well
balanced the system is.
6.6
View metering values
Measurements/Metering
The output data generated under metering is from the pulse counter and includes data
about the status of the counter and counter values.
Section 6
Read measured values
28
Operator's manual
1MRK504049-UEN rev. D
RET 670