9.2.8.6
Voltage sequence components (MSQI)
Settings/General settings/Monitoring/Voltage sequence components
The voltage sequence components part of the HMI under settings is where the user
sets the limits and deadband settings for voltage sequence components. The
designation for zero sequence voltage is 3U0, for positive sequence voltage is U1 and
for negative sequence voltage is U2.
There are three sets of settings with seven categories of parameter settings per set
(VSQ)
9.2.8.7
Disturbance report (RDRE)
Settings/General Settings/Monitoring/Disturbance Report
Displays seven settings.
9.2.8.8
Binary signals
Settings/General settings/Monitoring/Disturbance report/Binary signals/
Channel xx-yy
There are up to six groups of 16 channels with 16 binary outputs per channel. Each
channel has four settable parameters. These are operation, trig level, indication MA
and set LED.
9.2.8.9
Analog signals
Settings/General settings/Monitoring/Disturbance report/Analog signals/
Channel xx-yy
There are four groups of 10 channels with 10 analog signals per channel. Each signal
has six settable parameters such as operation, Nominal value and trig values.
9.2.8.10
Generic measured value
Settings/General Settings/Monitoring/Generic measured value
Sixteen instances of settings for the Measured Value function (MV) with 12 settable
parameters. These settings are used to define the range of values used in the function
block and to set the threshold values. This is a generic function and therefore the input
values depend on the application.
9.2.8.11
Event function
Settings/General settings/Monitoring/Event function
Section 9
Read and change settings
RET 670
Operator's manual
1MRK504049-UEN rev. D
43