Mounting methods and details
Chapter 5
Installing the IED
Depending on the wall different preparations may be needed like drilling
and inserting plastic or expander plugs (concrete/plasterboard walls) or
threading (metal sheet wall).
2.
Mount the DIN-rail(s) on the mounting bars.
3.
Mount the IED blocks on the DIN-rail(s).
It is much easier to do this without the unit in place.
4.
Make all external electrical connections to the IED terminal blocks.
It is much easier to do this without the unit in place.
5.
Mount the side plates (PosNo 6) to the IED.
6.
Mount the IED to the mounting bars.
3.4.3
Protection cover
The IED can be equipped with a rear protection cover (PosNo 1), which is recommended at this
type of mounting. See
figure 11
Figure 11:
Protection cover.
3.4.4
How to reach the rear side of the IED
To reach the rear side of the IED, a free space of 80 mm is required on the unhinged side.
PosNo
Description
1
Protection cover
xx04000454.vsd