60
About this chapter
Chapter 9
Establishing connection and
verifying the LON communication
Figure 24:
Example of LON communication structure for a substation automation system.
An optical network can be used within the Substation Automation system. This enables commu-
nication with the 670IEDs through the LON bus from the operator’s workplace, from the control
center and also from other IEDs via bay-to-bay horizontal communication.
The fiber optic LON bus is implemented using either glass core or plastic core fiber optic cables.
Table 9:
Specification of the fiber optic connectors
Glass fiber
Plastic fiber
Cable connector
ST-connector
snap-in connector
Cable diameter
62.5/125 m
1 mm
Max. cable length
1000 m
10 m
Wavelength
820-900 nm
660 nm
Transmitted power
-13 dBm (HFBR-1414)
-13 dBm (HFBR-1521)
Receiver sensitivity
-24 dBm (HFBR-2412)
-20 dBm (HFBR-2521)
Control Center
IED670
IED670
IED670
Gateway
Star coupler
RER 111
Station HSI
MicroSCADA
en05000663.vsd