![ABB RELION REL670 Installation And Commissioning Manual Download Page 184](http://html.mh-extra.com/html/abb/relion-rel670/relion-rel670_installation-and-commissioning-manual_4707184.webp)
176
Fault tracing
Chapter 13
Fault tracing and repair
The internal events are time tagged with a resolution of 1 ms and stored in a list. The list can
store up to 40 events. The list is based on the FIFO principle, when it is full, the oldest event is
overwritten. The list cannot be cleared; its content cannot be erased.
The internal events in this list not only refer to faults in the IED, but also to other activities, such
as change of settings, clearing of disturbance reports, and loss of external time synchronization.
The information can only be retrieved with the aid of the PST software package. The PC can be
connected either to the port at the front or at the rear of the IED.
These events are logged as internal events.
Table 24:
Events available for the internal event list in the IED
The events in the internal event list are time tagged with a resolution of 1 ms.
This means that when using the PC for fault tracing, it provides information on the:
•
Module that should be changed.
Event message:
Description
Generating signal:
INT--FAIL
Off
Internal fail status
INT--FAIL (reset event)
INT--FAIL
INT--FAIL (set event)
INT--WARNING
Off
Internal warning status
lNT--WARNING (reset event)
INT--WARNING
lNT--WARNING (set event)
INT--NUMFAIL
Off
Numerical module fatal error sta-
tus
INT--NUMFAIL (reset event)
INT--NUMFAIL
INT--NUMFAIL (set event)
INT--NUMWARN
Off
Numerical module non-fatal error
status
INT--NUMWARN (reset event)
INT--NUMWARN
INT--NUMWARN (set event)
IOn--Error
Off
In/Out module No. n status
IOn--Error (reset event)
IOn--Error
IOn--Error (set event)
ADMn-Error
Off
Analog/Digital module No. n sta-
tus
ADMn-Error (reset event)
ADMn-Error
ADMn-Error (set event)
MIM1-Error
Off
mA-input module status
MIM1-Error (reset event)
MIM1-Error
MIM1-Error (set event)
INT--RTC
Off
Real Time Clock (RTC) status
INT--RTC (reset event)
INT--RTC
INT--RTC (set event)
INT--TSYNC
Off
External time synchronization sta-
tus
INT--TSYNC (reset event)
INT--TSYNC
INT--TSYNC (set event)
INT--SETCHGD
Any settings in IED changed
DRPC-CLEARED
All disturbances in Disturbance
report cleared
Summary of Contents for RELION REL670
Page 8: ...Contents ...
Page 72: ...64 About this chapter Chapter 9 Establishing connection and verifying the LON communication ...
Page 174: ...166 Remote communication Chapter 11 Verifying settings by secondary injection ...
Page 190: ...182 Maintenance Chapter 13 Fault tracing and repair ...
Page 198: ...190 Glossary Chapter 14 Glossary ...