51
Checking the self supervision signals
Chapter 7
Energizing the IED
3
Checking the self supervision signals
3.1
Reconfiguring the IED
I/O modules configured as logical I/O modules (BIM, BOM or IOM) are supervised.
I/O modules that are not configured are not supervised.
Each logical I/O module has an error flag that indicates signal or module failure. The error flag
is also set when the physical I/O module of the correct type is not detected in the connected slot.
3.2
Setting the IED time
This procedure describes how to set the IED time from the local HMI.
1.
Display the set time dialog.
Navigate to:
Settings\Time\System time
Press the
E
button to enter the dialog.
2.
Set the date and time.
Use the
Left
and
Right
arrow buttons to move between the time and date
values (year, month, day, hours, minutes and seconds). Use the
Up
and
Down
arrow buttons to change the value.
3.
Confirm the setting.
Press the
E
button to set the calendar and clock to the new values.
3.3
Checking the self supervision function
3.3.1
Determine the cause of an internal failure
This procedure describes how to navigate the menus in order to find the cause of an internal fail-
ure when indicated by the flashing green LED on the HMI module.
Procedure
1.
Display the general diagnostics menu.
Navigate the menus to:
Diagnostics\IED status\General
2.
Scroll the supervision values to identify the reason for the failure.
Use the arrow buttons to scroll between values.
Summary of Contents for RELION REL670
Page 8: ...Contents ...
Page 72: ...64 About this chapter Chapter 9 Establishing connection and verifying the LON communication ...
Page 174: ...166 Remote communication Chapter 11 Verifying settings by secondary injection ...
Page 190: ...182 Maintenance Chapter 13 Fault tracing and repair ...
Page 198: ...190 Glossary Chapter 14 Glossary ...