81
Differential protection
Chapter 11
Verifying settings by secondary
injection
4
Differential protection
4.1
High impedance differential protection (PDIF, 87)
Prepare the IED for verification of settings as outlined in
section 1 "Overview" and section 2
in this chapter.
Procedure
1.
Connect single phase or three phase test set to inject the operating
voltage. The injection shall be on the primary side of the stabilizing
resistor.
Note! As the operating voltage is adjusted on the stabilizing resistor and
with the setting of the resistor value in the function this is essential for the
measurement of the expected value. Normally a slightly higher operating
value is no problem as the sensitivity is not influenced much.
2.
Connect the trip contact to the test set to stop the test set for mea-
surement of trip times below.
3.
Increase the voltage and make note of the operate value UR. This is
done with manual test and without trip of the test set.
4.
Reduce the voltage slowly and make note of the reset value. The re-
set value must be high for this function.
5.
Check the operating time by injecting a voltage corresponding to 1,2
UR> level Make note of the measured trip time.
6.
If required, verify the trip time at another voltage. Normally 2*UR is
selected.
7.
If used measure the alarm level operating value. Increase the voltage
and make note of the operate value U>Alarm. This is done with man-
ual test and without trip of the test set.
8.
Measure the operating time on the alarm output by connecting the
stop of the test set to an output from tAlarm. Inject a voltage
1,2*U>Alarm and measure the alarm time.
9.
Check that trip and alarm outputs operates according to the config-
uration logic.
10. Finally check that start and alarm information is stored in the Event
menu and if a serial connection to the SA is available verify that the
correct and only the required signals are presented on the local sta-
tion HMI and on the SCADA system.
Information on how to use the event menu is found in the REx670 operator's manual.
Summary of Contents for RELION REL670
Page 8: ...Contents ...
Page 72: ...64 About this chapter Chapter 9 Establishing connection and verifying the LON communication ...
Page 174: ...166 Remote communication Chapter 11 Verifying settings by secondary injection ...
Page 190: ...182 Maintenance Chapter 13 Fault tracing and repair ...
Page 198: ...190 Glossary Chapter 14 Glossary ...