147
Control
Chapter 11
Verifying settings by secondary
injection
Reset\Reset counters\AutoRecloser(RREC,79)\ARnn
2.
Restore settings that may have been modified for the tests back to
normal.
3.
Disconnect the test switch, CB simulating arrangement and test cir-
cuits.
Reconnect any links or connection terminals, which may have been
opened for the tests.
4.
Reset indications, alarms and disturbance recordings.
Clearing of the disturbance report must be done via the PCM600 using
the Disturbance handling tool.
5.
Continue to test other functions or complete the test by changing the
Test mode setting to Off.
Restore connections and settings to their original values, if they were
changed for test purposes.
11.3
Apparatus control (APC)
The apparatus control function consists of four types of function blocks, which are connected in
a delivery-specific way between bays and to the station level. For that reason, test the total func-
tion in a system, that is, either in a complete delivery system as an acceptance test (FAT/SAT)
or as parts of that system.
11.4
Interlocking
Prepare the IED for verification of settings as outlined in
section 1 "Overview" and section 2
in this chapter.
The interlocking function consists of a bay-level part and a station-level part. The interlocking
is delivery specific and is realized by bay-to-bay communication over the station bus. For that
reason, test the function in a system, that is, either in a complete delivery system as an accep-
tance test (FAT/SAT) or as parts of that system.
Summary of Contents for RELION REL670
Page 8: ...Contents ...
Page 72: ...64 About this chapter Chapter 9 Establishing connection and verifying the LON communication ...
Page 174: ...166 Remote communication Chapter 11 Verifying settings by secondary injection ...
Page 190: ...182 Maintenance Chapter 13 Fault tracing and repair ...
Page 198: ...190 Glossary Chapter 14 Glossary ...