t = Delay (1)
Trip
Send
Trip
Trip Weak
Send
Send Echo
Trip
Send
Trip
Send
Trip
Send
t = Com Rec :
t = Delay (Def) :
t = Delay (3) :
t = Delay (2) :
= 0 sec :
= Meas Main
= Meas Oreach * notTransbl
= (Com Rec + Unblock) * Meas Oreach * notTransbl
= Com Rec * Weak * notMeas Bward * notMeas Oreach
= Meas Oreach * notTransbl
= Com Rec * notMeas Bward
= Meas Main
= "0"
= Meas Main
= "0"
= Start L1+L2+L3 (dir/nondir)
= "0"
IEC19000429 V1 EN-US
POTT transmit logic (POTT_SEND)
GUID-994B7BE2-D432-4EA1-9F19-9D37D6B8F750 v1
AND
AND
AND
OR
AND
AND
AND
OR
P_PO TT
POTT_ON
MEAS_OR2
BI T_TBE
DELAY2
P_ECHO
100
EXTBLK_HF
HFREC
150
PO TT_SEND
MEAS_BWD
M_OWN
18000026-IEC19000430-1-en.vsdx
IEC19000430 V1 EN-US
Figure 27: POTT_SEND segment
Table 59: Signals POTT_SEND
Signal
In
Out
Source
Drain
P_POTT
X
Setting: Com Mode
POTTP_POTT= 1
MEAS_OR2
X
Binary output: Meas Oreach
BIT_TBE
X
Internal logic signal TRANSBL
DELAY2
X
Binary output: Delay 2
P_ECHO
X
Setting: Echo
On = 1; Off = 0
MEAS_BWD
X
Binary output: Meas Bward
M_OWN
X
Internal logic signal (TRIP2)
Table continues on next page
Section 5
1MRK 505 406-UEN B
Bay protection functions
76
Bay protection functions REB500
Technical manual
© Copyright 2019 ABB. All rights reserved