Text
Unit
Default
Min
Max
Step
Delay
s
1.00
0.02
60.00
0.01
tWait
s
0.20
0.02
20.00
0.01
MemDirMode
Select
Trip
(Select)
MemDuration
s
2.00
0.20
60.00
0.01
Receive
BinaryAddr
Always on
Ext Block
BinaryAddr
Always off
Trip
SignalAddr
Start
SignalAddr
Start L1
SignalAddr
Start L2
SignalAddr
Start L3
SignalAddr
MeasFwd
SignalAddr
MeasBwd
SignalAddr
5.5.5
Parameters
GUID-DF58F896-C3D7-4D23-98CE-4191FF983E9D v1
Table 76: Directional overcurrent inverse time function - parameters
Signal
Description
ParSet4..1
Parameter for determining in which set of parameters a particular function is
active
CurrentInp
Defines the CT input channel. Only three-phase CTs can be set
VoltageInp
Defines the VT input channel. Only three-phase VTs can be set
I-Setting
Pick-up current at which the characteristic becomes effective
Angle
Characteristic angle
c-Setting
Setting for the exponential factor determining the operating characteristic
according to BS 142
k
1
-Setting
Constant determining the parallel shift of the characteristic (time grading)
t-min
Definite minimum operating time, operating characteristic constant
IB-Setting
Base current for taking account of differences of rated current I
N
t
wait
Time allowed for the directional decision to be received
MemDirMode
determines the response of the protection after the time set for memorizing
power direction:
•
trip
•
block
MemDuration
Time during which the power direction last determined remains valid.
Receive
Input for the signal from the opposite end of the line:
•
T: not used
•
xx: all binary inputs (or outputs of protection functions)
Ext Block
•
F: not blocked
•
xx: all binary inputs (or outputs of protection functions)
Trip
Tripping signal
Start
Pick-up signal
Table continues on next page
Section 5
1MRK 505 406-UEN B
Bay protection functions
106
Bay protection functions REB500
Technical manual
© Copyright 2019 ABB. All rights reserved