I , I , I , I
L1
L2
L3
E
U , U , U , U
L1
L2
L3
E
START
N
Trip
N
Y
Z calculation
(ph-0 compensated)
Overcurrent
Stoping
Y
END
Signalling,
fault location,
Z(loop)
the timers
N
t > 1 periode
Loop =
phase selection
starter
Y
Change to
processing
periode II
Overcurrent
starter
Change to
processing
periode II
Z , Z , (Z ),
Start
1-4
OR
Z , direction
Back
18000014-IEC19000416-1-en.vsdx
IEC19000416 V1 EN-US
Figure 15: Processing period I
Measurement during processing period II
GUID-170FC07B-AEC8-4224-9871-EB915AC3D2FD v1
Processing period II commences after the first tripping signal or at the latest one period of the
system frequency after a starter picks up. The variables measured are the same as those
already processed during processing period I.
Only in the case of a cross-country fault in an ungrounded system or system with Petersen
coils is measurement restricted during processing period II to just the impedance loop
determined by the phase selection logic, otherwise all the phase-to-ground and phase-to-
Section 5
1MRK 505 406-UEN B
Bay protection functions
60
Bay protection functions REB500
Technical manual