5.11.4
Function settings
GUID-A7084910-3F39-4F82-994C-CB19D2C42F70 v1
Table 93: Logic function - settings
Text
Unit
Default
Min
Max
Step
ParSet 4..1
P1
(Select)
Logic Mode
OR
(Select)
BinOutput
SignalAddr
BlockInp
BinaryAddr
Always off
BinInp1 (R1)
BinaryAddr
Always off
BinInp2 (R2)
BinaryAddr
Always off
BinInp3 (S1)
BinaryAddr
Always off
BinInp4 (S2)
BinaryAddr
Always off
5.11.5
Parameters
GUID-FFD23A75-A981-4847-AA5D-AA085E47A10A v1
Table 94: Logic function - parameters
Signal
Description
ParSet 4..1
Parameter for determining in which set of parameters a particular function is active.
Logic Mode
Definition of the logic function to be performed by the 4 binary inputs. Possible
settings:
•
OR: OR gate with all 4 binary inputs
•
AND: AND gate with all 4 binary inputs
•
R/S flip-flop: Flip-flop with 2 set inputs (S1 and S2) and 2 reset inputs (R1 and
R2). The output is set or reset when at least one of the corresponding inputs is
at logical
1 (OR gate). Reset inputs take priority over the set inputs.
BinOutput
Output for signaling a trip (logic) respectively tripping (trip logic)
BlockInp
Input for blocking the function
•
F: not used
•
xx: all binary inputs (or outputs of protection functions)
The output is always at logical
0 when the blocking input is at logical 1. The blocking
input acts as a reset input for the flip-flop function.
BinInp (R1)
BinInp2 (R2)
BinInp3 (S1)
BinInp4 (S2)
Binary inputs 1 to 4 (AND or OR function)
Reset inputs 1 and 2 and set inputs 1 and 2 (RS flip-flop)
•
F: not used (OR logic or RS flip-flop in logic mode)
•
T: not used (AND logic in logic mode)
•
xx: all binary inputs (or outputs of protection functions)
5.12
Delay/Integrator (DELAY)
5.12.1
Mode of operation
GUID-B9A42598-E62D-4AAC-8FE6-8C1DA244A48C v1
General purpose timer for:
Section 5
1MRK 505 406-UEN B
Bay protection functions
174
Bay protection functions REB500
Technical manual