5.7.3.4
Measurements
GUID-E7D295D8-0041-4598-9D4D-135C13AB5E80 v1
Synchronism check (single-phase)
Voltage amplitude difference
(|dU|) = |UBus - ULine|
Phase-shift
(dPh) = PhBusbar - PhLine
Frequency difference
(|df|) = |fBus - fLine|
Voltage check (single or three-phase)
•
Max. busbar voltage (MaxuBus)
•
Min. busbar voltage (MinuBus)
•
Max. line voltage (MaxuLine)
•
Min. line voltage (MinuLine)
Single-phase:
max. voltage = min. voltage
Three-phase:
max. voltage = max. phase-to-phase voltage
min. voltage = min. phase-to-phase voltage
5.7.4
Function settings
GUID-6C0DF96A-18C4-4CC6-9AE8-078FDDBC55CA v1
Table 80: Synchrocheck function - settings
Text
Unit
Default
Min
Max
Step
ParSet 1..4
P1
(Select)
maxVoltDif
U
N
0.20
0.05
0.40
0.05
maxPhaseDif
deg
10.0
05.0
80.0
05.0
maxFreqDif
Hz
0.20
0.05
0.40
0.05
minVoltage
U
N
0.70
0.60
1.00
0.05
maxVoltage
U
N
0.30
0.10
1.00
0.05
Operat.-Mode
only SynChck
(Select)
supervisTime
s
0.20
0.05
5.00
0.05
t-Reset
s
0.05
0.00
1.00
0.05
uBusInp-Ph
1ph L1-L2
(Select)
uBusInput1
AnalogAddr
0
uBusInput2
AnalogAddr
0
uLineInp-Ph
1ph L1-L2
(Select)
uLineInput
AnalogAddr
0
uBus1Activ
BinaryAddr
Always on
uBus2Activ
BinaryAddr
Always off
ReleaseInp1
BinaryAddr
Always on
ReleaseInp2
BinaryAddr
Always off
BlckTrigBus1
BinaryAddr
Always off
BlckTrigBus2
BinaryAddr
Always off
BlckTrigLine
BinaryAddr
Always off
Table continues on next page
Section 5
1MRK 505 406-UEN B
Bay protection functions
116
Bay protection functions REB500
Technical manual
© Copyright 2019 ABB. All rights reserved