the sum of the three-phase currents
•
the sequence of the three-phase currents
•
provision for comparing the sum of the three-phase currents with a residual current input
•
adjustment of residual current amplitude
•
blocking at high currents (higher than 2 × I
N
)
•
blocking of phase-sequence monitoring at low currents (below 0.05 × I
N
)
•
insensitive to DC components
•
insensitive to harmonics
5.13.3
Inputs and outputs
5.13.3.1
CT/VT inputs
GUID-6903FDD9-78BE-4BC7-BBBE-DB3C1ED26353 v1
•
Phase currents
5.13.3.2
Binary inputs
GUID-B5C04044-60D7-4FF6-B074-B7B6B9A18308 v1
•
Blocking
5.13.3.3
Binary outputs
GUID-5C506AEB-CB08-4C01-A40F-A781D202DD3F v1
•
Tripping
5.13.3.4
Measurements
GUID-16C59088-A3A6-4D1B-BC6A-F25743D4CEF4 v1
•
Difference between the vector sum of the three-phase currents and the neutral current
5.13.4
Function settings
GUID-A1348575-07E6-4E14-A2B9-3A194AA0B057 v1
Table 97: Three-phase current plausibility function - settings
Text
Unit
Default
Min
Max
Step
ParSet 4..1
P1 (Select)
(Select)
I-Setting
I
N
0.20
0.05
1.00
0.05
Delay
s
10.00
0.1
60.0
0.1
CT-Compens
01.00
-2.00
2.00
0.01
CurrentInp
CT/VT-Addr
CT-I1-I3
BlockInp
BinaryAddr
Always off
Trip
SignalAddr
1MRK 505 406-UEN B
Section 5
Bay protection functions
Bay protection functions REB500
179