18000055-IEC19000460-1-en.vsdx
T rip CB
Star t
Close CB
Z Extension
Def. T rip
F ir st AR 1P
T rip CB 3P
AR in Pro g.
AR R eady
AR Blocked
T rip 3- Pol
Main protection 2, AR blocked (
because
main protection 1 ready)
Main protection 1, AR ready
T rip CB
Star t
Close CB
Z Extension
Def. T rip
F ir st AR 1P
T rip CB 3P
AR in Pro g.
AR R eady
AR Blocked
t inhibit.
t De ad1 1P
time < t Oper.
T rip 3- Pol
t D iscrim. 1P
t clo se
300 ms
IEC19000460 V1 EN-US
Figure 56: Timing diagram for scheme with main protections 1 and 2 (REB500sys), both
equipped with an autoreclosure function — Main protection 1 is in operation
>> Response for successful autoreclosure
Settings:
•
1. AR Mode = 1P-1P or 1P3P-1P3P
•
2..4. AR Mode = off
•
Zextension = on
•
ZE 1. AR = off
1MRK 505 406-UEN B
Section 5
Bay protection functions
Bay protection functions REB500
151
Technical manual