Permissive underreaching transfer tripping (PUTT)
GUID-666A852F-90EE-4C7D-BF10-B16BFE5DDD69 v1
The criteria for tripping and transmission of a transfer trip signal by the distance protection
function in a PUTT scheme are given in the tabular overview below.
t = Delay (1)
Trip
Send
Trip (PUTT NONDIR)
Trip (PUTT FWD)
Trip (PUTT OR2)
Send
Trip
Send
Trip
Send
Trip
Send
t = Com Rec :
t = Delay (Def) :
t = Delay (3) :
t = Delay (2) :
= 0 sec :
= Meas Main
= Meas Main
= Com Rec * (Start L1+L2+L3 + Weak)
= Com Rec * Meas Fward
= (Com Rec + Unblock) * Meas Oreach
= Meas Main
= Meas Main
= Meas Main
= Meas Main
= "0"
= Start L1+L2+L3 (dir/nondir)
= "0"
IEC19000426 V1 EN-US
PUTT transmit logic (PUTT_SEND)
GUID-DBE31BF6-F8DB-4CE9-90F5-A256D838FC8D v1
The logic (PUTT_SEND) transfers its output signals to a common transmit logic for PUTT,
POTT and BLOCK OR schemes.
AND
PUTT ON
PUTT SEND
PUTT NONDIR
PUTT FWD
PUTT OR
OR
DELAY3
MEAS MAIN
START LI L2L3
18000024-IEC19000427-1-en.vsdx
IEC19000427 V1 EN-US
Figure 25: PUTT_SEND segment
Table 57: Signals PUTT_SEND (see above diagram)
Signal
In
Out
Source
Drain
PUTT_NONDIR
PUTT_FWD
PUTT_OR
X
Setting: Com Mode
PUTT non-directional
:
PUTT_NONDIR = 1
PUTT Forwards: PUTT_FWD = 1
PUTT OR2
: PUTT_BWD = 1
DELAY3
X
Binary output: Delay 3
MEAS_MAIN
X
Binary output: Meas Main
START_L1L2L3
X
Binary output: Start L1+L2+L3
PUTT_ON
X
Internal signal to the
distance function
transmit logic
(SENDLOGIC)
PUTT_SEND
X
Internal signal to the
distance function
transmit logic
1MRK 505 406-UEN B
Section 5
Bay protection functions
Bay protection functions REB500
73
Technical manual
© Copyright 2019 ABB. All rights reserved