Step REB500
configuration tool
HMI500
System
engineering tool
Remark
8
Final
configuration: The
assignment of
GOOSE data
attributes from
selection list
Unassigned
GOOSE data
attributes to
REB500 input
signals is made
-
9
Download the
configuration to
the REB500
system
-
CCF creator uses the information of the Station configuration
description (SCD) and of the REB500 configuration to create
the configuration of the REB500 GOOSE client Sending IED:
•
Communication section
•
GSEC Control
•
DataSet
This configuration is automatically created
during setfile download and the same time,
the CID/IID file is updated.
10
Post-
configuration:
Transfer of the
updated CID/IID
file (see remark
under item 9) to
the system
engineering tool
-
Used source IED data attributes are marked.
11
-
Post-
configuration:
Import of the
updated CID/IID
file
Prevents removing used GOOSE data attributes from the
source IED.
If any further configuration changes affect the IEC61850 model or IEC61850
communication, then the information should be transferred by repeating steps
2 through 11.
4.6.4.2
Enabling GOOSE Client
GUID-D2A41405-8484-45BC-B5E2-82EEE0FD8D9B v1
This section describes the pre-configuration of the GOOSE Client.