7.2.3
Alarm and Event list entries
GUID-74496126-BC60-41E1-B3A4-9D3A071593E8 v2
Description
Possible Cause
Corrective Action
1
General alarm
CU/BU
Check
Wrong BU address
Correct BU address
2
Differential current
alarm CU
CT circuit fault
Busbar image error
Check isolator image
Hardware failure
Replace CU/BU
3
Isolator alarm BU
Wrong binary connection to auxiliary contacts
Check connection dia-grams and
connections to the auxiliary
contacts
Wrong battery voltage configured
Correct setting (setfile)
Hardware failure
Replace BU
4
Invalid Time
Stamps
Wrong time synchronization type and/or
parameter
Check time synchronization type
and/or parameter
Wrong time master configuration
Check time master configuration
Wrong LWL connections
Check LWL connections to time
master
5
Hardware
Mismatch Alarm
Wrong hardware installed
Replace Hardware with
configured type.
Wrong hardware type configured
Change the configuration
6
IP address conflict
Ethernet interface LAN0 has address
configured which already exists in the network
connected to this interface
Change configured IP address
7
RPB Interruption
Alarm on BU
Process Bus connection interrupted
Check process bus connection
(see
CU is offline (for example, during a CU restart)
Wait until CU is up and running
again (up to 3 Minutes)
BU is stuck in standalone mode
Restart the BU
8
RPB Interruption
Alarm on CU
At least one of the two process bus links of the
CU is interrupted
Check both process bus links
(see
7.2.4
Optical fiber connections faults
GUID-36722875-6514-4090-9FEE-70207E0F99DD v1
Description
Possible Cause
Corrective Action
1
Process Bus:
No link LED for a connected
BU
Optical fiber defect, or wrong
type
Check, replace optical
fibers
Optical fiber wrong connection
Check connection
2
IEC 61850 Bus
No link LED for a connected
station control system
Optical fiber defect, or wrong
type
Check, replace optical
fibers
Optical fiber wrong connection
Check connection
3
IEC 103 RX/TX LED dose
not blink
Optical fiber defect, or wrong
type
Check optical fibers
Optical fiber wrong connection
Check optical fiber
connections
Wrong IEC103 Configuration
Check IEC103
Configuration
1MRK 500 132-UEN B
Section 7
Troubleshooting
Distributed busbar protection REB500
91
Operation manual
© Copyright 2019 ABB. All rights reserved