4.6.3.6
Outputs Overview tab
GUID-DEDABA49-152E-46C5-AD22-9575930BB534 v2
13000008-IEC18000540-1-en.vsdx
IEC18000540 V1 EN-US
Figure 30: Configuration/ Binary module/ Outputs/ Overview – CU
13000009-IEC18000541-1-en.vsdx
IEC18000541 V1 EN-US
Figure 31: Configuration/ Binary module/ Outputs/ Overview – BU
The overview of the BU outputs shows which signals are assigned to which output relays. An
output relay can be controlled by several signals (for example, relay CR02 by TRIP and BFP
TRIP).
For reasons of safety, it is impossible to mix tripping commands and signals, that is tripping
commands can only be combined with tripping commands and control signals with control
signals.
Tripping commands:
Section 4
1MRK 500 132-UEN B
HMI500
38
Distributed busbar protection REB500
Operation manual
© Copyright 2019 ABB. All rights reserved