15000037-IEC18000557-1-en.vsdx
IEC18000557 V1 EN-US
Figure 39: GOOSE data attributes imported
To simplify GOOSE engineering in REB500, the import of GOOSE signals is
limited to specific logical nodes (for example, PTRC).
4.6.4.5
GOOSE input mapping
GUID-412DEE24-DC4A-4536-9699-43BC440EBEC2 v1
This section describes the configuration process of GOOSE input mapping in HMI500 menu
Configuration/Binary Module/Inputs/Details.
15000042-IEC18000562-1-en.vsdx
IEC18000562 V1 EN-US
Figure 40: Configuration/ Binary module/ Inputs/ Details/ Contact mode – GOOSE Input
Table 11: GOOSE Input menu items
Menu Items
Description
Assigned GOOSE data
Attribute
If a REB500 Signal has assigned to a GOOSE data attribute then the
name of the attribute is listed in this field
Selection – Unassigned
GOOSE data Attributes
List of GOOSE data attributes which can be assigned to the
.
Selection – Assign
Confirms the mapping of the selected attribute to the REB500
Signal. The Assign button is enabled after the Station
configuration file (SCD) has been imported.
Selection – Deassign
Breaks the connection between the GOOSE data attribute and the
REB500 input signal. The GOOSE data attribute can be assigned to
another REB500 Signal.
Selection – GOOSE data
attribute filter
See
1MRK 500 132-UEN B
Section 4
HMI500
Distributed busbar protection REB500
47
Operation manual
© Copyright 2019 ABB. All rights reserved