DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
BndCtrPar
v2_dMV
mag.f
MX
-
USETPAR
Mon
Average voltage setpoint used in
parallel mode
q
MX
-
USETPAR
Mon
Quality: Average voltage setpoint
used in parallel mode
t
MX
-
USETPAR
Mon
Timestamp: Average voltage
setpoint used in parallel mode
BndCtrSet
v2_dMV
mag.f
MX
-
-
Mon
Voltage setpoint set by user
q
MX
-
-
Mon
Quality: Voltage setpoint set by
user
t
MX
-
-
Mon
Timestamp: Voltage setpoint set
by user
CircALim
v2_dMV
mag.f
MX
-
-
Mon
Block level of circulating current
q
MX
-
-
Mon
Quality: Block level of circulating
current
t
MX
-
-
Mon
Timestamp: Block level of
circulating current
LVA1V
v2_dMV
mag.f
MX
-
-
Mon
Value 1 for load voltage
adjustment
q
MX
-
-
Mon
Quality: Value 1 for load voltage
adjustment
t
MX
-
-
Mon
Timestamp: Value 1 for load
voltage adjustment
LVA2V
v2_dMV
mag.f
MX
-
-
Mon
Value 2 for load voltage
adjustment
q
MX
-
-
Mon
Quality: Value 2 for load voltage
adjustment
t
MX
-
-
Mon
Timestamp: Value 2 for load
voltage adjustment
LVA3V
v2_dMV
mag.f
MX
-
-
Mon
Value 3 for load voltage
adjustment
q
MX
-
-
Mon
Quality: Value 3 for load voltage
adjustment
t
MX
-
-
Mon
Timestamp: Value 3 for load
voltage adjustment
LVA4V
v2_dMV
mag.f
MX
-
-
Mon
Value 4 for load voltage
adjustment
q
MX
-
-
Mon
Quality: Value 4 for load voltage
adjustment
t
MX
-
-
Mon
Timestamp: Value 4 for load
voltage adjustment
AvBusV
v2_dMV
mag.f
MX
-
-
Mon
Average of measured busbar
voltage (service value)
q
MX
-
-
Mon
Quality: Average of measured
busbar voltage (service value)
t
MX
-
-
Mon
Timestamp: Average of measured
busbar voltage (service value)
CircV
v2_dMV
mag.f
MX
-
-
Mon
Calculated circulating voltage
Table continues on next page
Section 7
1MRK 511 349-UEN -
Logical node data model
72
670 series 2.1 IEC
Communication protocol manual