Table 57:
ZGVPDIS Logical node data (instance 1)
DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Beh
a_dINS
stVal
ST
-
Beh
Mon
Behaviour parameter for 61850
q
ST
-
Beh
Mon
Quality: Behaviour parameter for
61850
t
ST
-
Beh
Mon
Timestamp: Behaviour parameter
for 61850
Str
b_dACD
general
ST
-
STUV
Mon
Start of under voltage seal in
q
ST
-
STUV
Mon
Quality: Start of under voltage seal
in
t
ST
-
STUV
Mon
Timestamp: Start of under voltage
seal in
Op
b_dACT
general
ST
T
TRUV
Mon
Trip from Under voltage seal in
q
ST
T
TRUV
Mon
Quality: Trip from Under voltage
seal in
t
ST
T
TRUV
Mon
Timestamp: Trip from Under
voltage seal in
Mod
c_dINC
stVal
ST
-
-
Mon
Mode status value parameter for
61850
q
ST
-
-
Mon
Quality: Mode status value
parameter for 61850
t
ST
-
-
Mon
Timestamp: Mode status value
parameter for 61850
7.5.4
Directional overpower PDOP
7.5.4.1
Directional over-power protection GOPPDOP
LN type
LN prefix LN class Function block name
GOPPDOP (revision 1) GOP
PDOP
GOPPDOP
Table 58:
GOPPDOP Logical node data
DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Mod
a_dINC
Oper.ctlVal
CO
-
Mod
Cmd
Mode parameter
Oper.origin.orCat
CO
-
Mod
Cmd
Mode parameter
Oper.origin.orIdent
CO
-
Mod
Cmd
Mode parameter
Oper.ctlNum
CO
-
Mod
Cmd
Mode parameter
Oper.T
CO
-
Mod
Cmd
Mode parameter
Oper.Test
CO
-
Mod
Cmd
Mode parameter
Oper.Check
CO
-
Mod
Cmd
Mode parameter
stVal
ST
-
-
Mon
Mode status parameter for 61850
Table continues on next page
1MRK 511 349-UEN -
Section 7
Logical node data model
670 series 2.1 IEC
149
Communication protocol manual