Table 80:
EF4PTOC Logical node data (instance 2)
DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Beh
a_dINS
stVal
ST
-
Beh
Mon
Behaviour parameter for 61850
q
ST
-
Beh
Mon
Quality: Behaviour parameter for
61850
t
ST
-
Beh
Mon
Timestamp: Behaviour parameter
for 61850
Str
b_dACD
general
ST
-
STIN2
Mon
Start signal step 2
q
ST
-
STIN2
Mon
Quality: Start signal step 2
t
ST
-
STIN2
Mon
Timestamp: Start signal step 2
Op
b_dACT
general
ST
T
TRIN2
Mon
Trip signal from step 2
q
ST
T
TRIN2
Mon
Quality: Trip signal from step 2
t
ST
T
TRIN2
Mon
Timestamp: Trip signal from step 2
Mod
c_dINC
stVal
ST
-
-
Mon
Mode status value parameter for
61850
q
ST
-
-
Mon
Quality: Mode status value
parameter for 61850
t
ST
-
-
Mon
Timestamp: Mode status value
parameter for 61850
Table 81:
EF4PTOC Logical node data (instance 3)
DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Beh
a_dINS
stVal
ST
-
Beh
Mon
Behaviour parameter for 61850
q
ST
-
Beh
Mon
Quality: Behaviour parameter for
61850
t
ST
-
Beh
Mon
Timestamp: Behaviour parameter
for 61850
Str
b_dACD
general
ST
-
STIN3
Mon
Start signal step 3
q
ST
-
STIN3
Mon
Quality: Start signal step 3
t
ST
-
STIN3
Mon
Timestamp: Start signal step 3
Op
b_dACT
general
ST
T
TRIN3
Mon
Trip signal from step 3
q
ST
T
TRIN3
Mon
Quality: Trip signal from step 3
t
ST
T
TRIN3
Mon
Timestamp: Trip signal from step 3
Mod
c_dINC
stVal
ST
-
-
Mon
Mode status value parameter for
61850
q
ST
-
-
Mon
Quality: Mode status value
parameter for 61850
t
ST
-
-
Mon
Timestamp: Mode status value
parameter for 61850
1MRK 511 349-UEN -
Section 7
Logical node data model
670 series 2.1 IEC
175
Communication protocol manual