Table 34:
ZMRPDIS Logical node data
DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Str
aACD
general
ST
-
START
Mon
General Start, issued from any
phase or loop
dirGeneral
ST
-
-
Mon
Integer coded info about general
direction of fault
phsA
ST
-
STL1
Mon
Start signal from phase L1
phsB
ST
-
STL2
Mon
Start signal from phase L2
phsC
ST
-
STL3
Mon
Start signal from phase L3
q
ST
-
START
Mon
Quality: General Start, issued from
any phase or loop
t
ST
-
START
Mon
Timestamp: General Start, issued
from any phase or loop
Op
aACT
general
ST
T
TRIP
Mon
General Trip, issued from any
phase or loop
phsA
ST
T
TRL1
Mon
Trip signal from phase L1
phsB
ST
T
TRL2
Mon
Trip signal from phase L2
phsC
ST
T
TRL3
Mon
Trip signal from phase L3
q
ST
T
TRIP
Mon
Quality: General Trip, issued from
any phase or loop
t
ST
T
TRIP
Mon
Timestamp: General Trip, issued
from any phase or loop
Mod
aINC
Oper.ctlVal
CO
-
Mod
Cmd
Mode parameter
Oper.origin.orCat
CO
-
Mod
Cmd
Mode parameter
Oper.origin.orIdent
CO
-
Mod
Cmd
Mode parameter
Oper.ctlNum
CO
-
Mod
Cmd
Mode parameter
Oper.T
CO
-
Mod
Cmd
Mode parameter
Oper.Test
CO
-
Mod
Cmd
Mode parameter
Oper.Check
CO
-
Mod
Cmd
Mode parameter
stVal
ST
-
-
Mon
Mode status parameter for 61850
q
ST
-
-
Mon
Quality: Mode status parameter for
61850
t
ST
-
-
Mon
Timestamp: Mode status
parameter for 61850
Beh
aINS
stVal
ST
-
Beh
Mon
Behaviour parameter for 61850
q
ST
-
Beh
Mon
Quality: Behaviour parameter for
61850
t
ST
-
Beh
Mon
Timestamp: Behaviour parameter
for 61850
StrNDir
v1SPS
stVal
ST
-
STND
Mon
Non-directional start, issued from
any phase or loop
q
ST
-
STND
Mon
Quality: Non-directional start,
issued from any phase or loop
t
ST
-
STND
Mon
Timestamp: Non-directional start,
issued from any phase or loop
Section 7
1MRK 511 349-UEN -
Logical node data model
130
670 series 2.1 IEC
Communication protocol manual