DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Str
b_dACD
q
ST
-
STOC2
Mon
Quality: Start signal from
overcurrent function OC2
t
ST
-
STOC2
Mon
Timestamp: Start signal from
overcurrent function OC2
Op
b_dACT
general
ST
T
TROC2
Mon
Trip signal from overcurrent
function OC2
q
ST
T
TROC2
Mon
Quality: Trip signal from
overcurrent function OC2
t
ST
T
TROC2
Mon
Timestamp: Trip signal from
overcurrent function OC2
Mod
c_dINC
stVal
ST
-
-
Mon
Mode status parameter for 61850
q
ST
-
-
Mon
Quality: Mode status parameter for
61850
t
ST
-
-
Mon
Timestamp: Mode status
parameter for 61850
IvdCrv
v1_dSPS
stVal
ST
-
-
Mon
Error signal from overcurrent
function OC2
q
ST
-
-
Mon
Quality: Error signal from
overcurrent function OC2
t
ST
-
-
Mon
Timestamp: Error signal from
overcurrent function OC2
Table 181:
CVGAPC Logical node data (instance 1)
DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Beh
a_dINS
stVal
ST
-
Beh
Mon
Behaviour parameter for 61850
q
ST
-
Beh
Mon
Quality: Behaviour parameter for
61850
t
ST
-
Beh
Mon
Timestamp: Behaviour parameter
for 61850
Str
b_dACD
general
ST
-
STOC1
Mon
Start signal from overcurrent
function OC1
dirGeneral
ST
-
DIROC1
Mon
Directional mode of OC1 (nondir,
forward,reverse)
q
ST
-
STOC1
Mon
Quality: Start signal from
overcurrent function OC1
t
ST
-
STOC1
Mon
Timestamp: Start signal from
overcurrent function OC1
Op
b_dACT
general
ST
T
TROC1
Mon
Trip signal from overcurrent
function OC1
q
ST
T
TROC1
Mon
Quality: Trip signal from
overcurrent function OC1
t
ST
T
TROC1
Mon
Timestamp: Trip signal from
overcurrent function OC1
Mod
c_dINC
stVal
ST
-
-
Mon
Mode status parameter for 61850
Table continues on next page
Section 7
1MRK 511 349-UEN -
Logical node data model
250
670 series 2.1 IEC
Communication protocol manual