
Table 6:
SCILO Logical node data
DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Mod
aINC
Oper.ctlVal
CO
-
Mod
Cmd
Mode parameter
Oper.origin.orCat
CO
-
Mod
Cmd
Mode parameter
Oper.origin.orIdent
CO
-
Mod
Cmd
Mode parameter
Oper.ctlNum
CO
-
Mod
Cmd
Mode parameter
Oper.T
CO
-
Mod
Cmd
Mode parameter
Oper.Test
CO
-
Mod
Cmd
Mode parameter
Oper.Check
CO
-
Mod
Cmd
Mode parameter
stVal
ST
-
-
Mon
Mode status parameter for 61850
q
ST
-
-
Mon
Quality: Mode status parameter for
61850
t
ST
-
-
Mon
Timestamp: Mode status
parameter for 61850
Beh
aINS
stVal
ST
-
Beh
Mon
Behaviour parameter
q
ST
-
Beh
Mon
Quality: Behaviour parameter
t
ST
-
Beh
Mon
Timestamp: Behaviour parameter
EnaCls
aSPS
stVal
ST
-
EN_CLOSE
Mon
Close operation at open or interm.
or bad pos. is enabled
q
ST
-
EN_CLOSE
Mon
Quality: Close operation at open or
interm. or bad pos. is enabled
t
ST
-
EN_CLOSE
Mon
Timestamp: Close operation at
open or interm. or bad pos. is
enabled
EnaOpn
aSPS
stVal
ST
-
EN_OPEN
Mon
Open operation at closed or
interm. or bad pos. is enabled
q
ST
-
EN_OPEN
Mon
Quality: Open operation at closed
or interm. or bad pos. is enabled
t
ST
-
EN_OPEN
Mon
Timestamp: Open operation at
closed or interm. or bad pos. is
enabled
7.3.3
Switch controller CSWI
7.3.3.1
Switch controller SCSWI
LN type
LN prefix LN class Function block name
SCSWI (revision 1) S
CSWI
SCSWI
1MRK 511 349-UEN -
Section 7
Logical node data model
670 series 2.1 IEC
79
Communication protocol manual