Figure 31: Fault time with maintained selectivity
To assure selectivity between different protections, in the radial network, there have to be a
minimum time difference
D
t between the time delays of two protections. The minimum time
difference can be determined for different cases. To determine the shortest possible time
difference, the operation time of protections, breaker opening time and protection resetting time
must be known. These time delays can vary significantly between different protective equipment.
The following time delays can be estimated:
Protection operation
time:
15-60 ms
Protection resetting
time:
15-60 ms
Breaker opening time:
20-120 ms
Example for time coordination
Assume two substations A and B directly connected to each other via one line, as shown in the
figure
. Consider a fault located at another line from the station B. The fault current to the
overcurrent protection of IED B1 has a magnitude so that the protection will have instantaneous
function. The overcurrent protection of IED A1 must have a delayed function. The sequence of
events during the fault can be described using a time axis, see figure
Section 7
1MRK 505 287-UUS B
Current protection
78
Busbar protection REB650
Application manual
© Copyright 2013 ABB. All rights reserved
Summary of Contents for RELION 650 SERIES
Page 1: ...Relion 650 SERIES Busbar protection REB650 Version 1 3 ANSI Application manual...
Page 2: ......
Page 22: ...16...
Page 34: ...28...
Page 56: ...50...
Page 64: ...58...
Page 76: ...70...
Page 120: ...114...
Page 184: ...178...
Page 216: ...210...
Page 220: ...214...
Page 254: ...248...
Page 261: ...255...