en04000491_ansi.vsd
S1S2OPTR (A1A2)
BC12OPTR (sect.1)
1289OPTR (bay 1/sect.2)
1289OPTR (bay n/sect.2)
S1S2OPTR (A1A2)
BC12OPTR (sect.2)
1289OPTR (bay 1/sect.1)
1289OPTR (bay n /sect.1)
BBTR_OP
VP_BBTR
EXDU_12
OR
AND
OR
AND
. . .
. . .
. . .
. . .
AND
AND
VPS1S2TR (A1A2)
VPBC12TR (sect.1)
VP1289TR (bay 1/sect.2)
VP1289TR (bay n/sect.1)
. . .
. . .
VPBC12TR (sect.2)
VP1289TR (bay 1/sect.1)
VP1289TR (bay n/sect.1)
. . .
. . .
AND
EXDU_12(bay 1/sect.2)
EXDU_12 (bay n /sect.2)
EXDU_12 (bay 1/sect.1)
EXDU_12 (bay n /sect.1)
EXDU_BS (A1A2)
EXDU_BC (sect.1)
EXDU_BC (sect.2)
. . .
. . .
. . .
. . .
ANSI04000491 V1 EN-US
Figure 67: Signals from any bays for a bus-section circuit breaker between sections B1 and
B2
10.3.5.3
Configuration setting
M15111-57 v3
If there is no other busbar via the busbar loops that are possible, then either the interlocking for
the 152 open circuit breaker is not used or the state for BBTR is set to open. That is, no busbar
transfer is in progress in this bus-section:
•
BBTR_OP = 1
•
VP_BBTR = 1
10.3.6
Interlocking for bus-section disconnector A1A2_DC (3)
IP14159-1 v2
Section 10
1MRK 505 287-UUS B
Control
150
Busbar protection REB650
Application manual
© Copyright 2013 ABB. All rights reserved