WA1 (A1)
289
489G
189
389G
WA2 (A2)
en04000516_ansi.vsd
289G
189G
A1A2_BS
152
ANSI04000516 V1 EN-US
Figure 64: Switchyard layout A1A2_BS (3)
M15111-4 v2
The signals from other bays connected to the module A1A2_BS are described below.
10.3.5.2
Signals from all feeders
M15111-6 v3
If the busbar is divided by bus-section circuit breakers into bus-sections and both circuit breakers
are closed, the opening of the circuit breaker must be blocked if a bus-coupler connection exists
between busbars on one bus-section side and if on the other bus-section side a busbar transfer is
in progress:
en04000489_ansi.vsd
Section 1
Section 2
A1A2_BS
B1B2_BS
ABC_LINE
ABC_BC
ABC_LINE
ABC_BC
(WA1)A1
(WA2)B1
(WA7)C
C
B2
A2
AB_TRAFO
AB_TRAFO
ANSI04000489 V1 EN-US
Figure 65: Busbars divided by bus-section circuit breakers
The interlocking functionality in 650 series can not handle the transfer bus (WA7)C.
To derive the signals:
Signal
BBTR_OP
No busbar transfer is in progress concerning this bus-section.
VP_BBTR
The switch status of BBTR is valid.
EXDU_12
No transmission error from any bay connected to busbar 1(A) and 2(B).
1MRK 505 287-UUS B
Section 10
Control
Busbar protection REB650
147
Application manual
© Copyright 2013 ABB. All rights reserved
Summary of Contents for RELION 650 SERIES
Page 1: ...Relion 650 SERIES Busbar protection REB650 Version 1 3 ANSI Application manual...
Page 2: ......
Page 22: ...16...
Page 34: ...28...
Page 56: ...50...
Page 64: ...58...
Page 76: ...70...
Page 120: ...114...
Page 184: ...178...
Page 216: ...210...
Page 220: ...214...
Page 254: ...248...
Page 261: ...255...