These signals from each bus-section disconnector bay (A1A2_DC) are also needed. For B1B2_DC,
corresponding signals from busbar B are used. The same type of module (A1A2_DC) is used for
different busbars, that is, for both bus-section disconnector A1A2_DC and B1B2_DC.
Signal
DCOPTR
The bus-section disconnector is open.
DCCLTR
The bus-section disconnector is closed.
VPDCTR
The switch status of bus-section disconnector DC is valid.
EXDU_DC
No transmission error from the bay that contains the above information.
If the busbar is divided by bus-section circuit breakers, the signals from the bus-section coupler
bay (A1A2_BS), rather than the bus-section disconnector bay (A1A2_DC) must be used. For
B1B2_BS, corresponding signals from busbar B are used. The same type of module (A1A2_BS) is
used for different busbars, that is, for both bus-section circuit breakers A1A2_BS and B1B2_BS.
Signal
S1S2OPTR
No bus-section coupler connection between bus-sections 1 and 2.
S1S2CLTR
A bus-section coupler connection exists between bus-sections 1 and 2.
VPS1S2TR
The switch status of bus-section coupler BS is valid.
EXDU_BS
No transmission error from the bay that contains the above information.
For a line bay in section 1, these conditions are valid:
1MRK 505 287-UUS B
Section 10
Control
Busbar protection REB650
169
Application manual
© Copyright 2013 ABB. All rights reserved
Summary of Contents for RELION 650 SERIES
Page 1: ...Relion 650 SERIES Busbar protection REB650 Version 1 3 ANSI Application manual...
Page 2: ......
Page 22: ...16...
Page 34: ...28...
Page 56: ...50...
Page 64: ...58...
Page 76: ...70...
Page 120: ...114...
Page 184: ...178...
Page 216: ...210...
Page 220: ...214...
Page 254: ...248...
Page 261: ...255...