The project-specific logic is the same as for the logic for the double-breaker configuration.
Signal
S1DC_OP
All disconnectors on bus-section 1 are open.
S2DC_OP
All disconnectors on bus-section 2 are open.
VPS1_DC
The switch status of disconnectors on bus-section 1 is valid.
VPS2_DC
The switch status of disconnectors on bus-section 2 is valid.
EXDU_BB
No transmission error from breaker and a half (BH) that contains the above
information.
10.3.7
Interlocking for bus-coupler bay ABC_BC (3)
IP14144-1 v2
10.3.7.1
Application
M13555-3 v7
The interlocking for bus-coupler bay (ABC_BC, 3) function is used for a bus-coupler bay connected
to a double busbar arrangement according to figure
. The function can also be used for a single
busbar arrangement with transfer busbar or double busbar arrangement without transfer busbar.
189
289
189G
WA1 (A)
WA2 (B)
WA7 (C)
789
2089
289G
en04000514_ansi.vsd
152
ANSI04000514 V1 EN-US
Figure 80: Switchyard layout ABC_BC (3)
The interlocking functionality in 650 series can not handle the transfer bus WA7(C).
10.3.7.2
Configuration
M13553-138 v3
The signals from the other bays connected to the bus-coupler module ABC_BC are described
below.
Section 10
1MRK 505 287-UUS B
Control
158
Busbar protection REB650
Application manual
© Copyright 2013 ABB. All rights reserved
Summary of Contents for RELION 650 SERIES
Page 1: ...Relion 650 SERIES Busbar protection REB650 Version 1 3 ANSI Application manual...
Page 2: ......
Page 22: ...16...
Page 34: ...28...
Page 56: ...50...
Page 64: ...58...
Page 76: ...70...
Page 120: ...114...
Page 184: ...178...
Page 216: ...210...
Page 220: ...214...
Page 254: ...248...
Page 261: ...255...