new pre-fault- and fault-time (which will overlap previous report)
•
events and indications might be saved in the previous report too, due to overlap
•
new trip value calculations if installed, in operation and started
Operation in test mode
M12179-492 v4
If the IED is in test mode and
OpModeTest = Disabled. Disturbance report function does not save
any recordings and no LED information is displayed.
If the IED is in test mode and
OpModeTest = Enabled. Disturbance report function works in normal
mode and the status is indicated in the saved recording.
12.7.3.1
Binary input signals
M12179-90 v6
Up to 96 binary signals can be selected among internal logical and binary input signals. The
configuration tool is used to configure the signals.
For each of the 96 signals, it is also possible to select if the signal is to be used as a trigger for the
start of the Disturbance report and if the trigger should be activated on positive (1) or negative (0)
slope.
TrigDRN: Disturbance report may trig for binary input N (Enabled) or not (Disabled).
TrigLevelN: Trig on positive (Trig on 1) or negative (Trig on 0) slope for binary input N.
12.7.3.2
Analog input signals
M12179-92 v4
Up to 40 analog signals can be selected among internal analog and analog input signals. PCM600
is used to configure the signals.
The analog trigger of Disturbance report is not affected if analog input M is to be included in the
disturbance recording or not (
OperationM = Enabled/Disabled).
If
OperationM = Disabled, no waveform (samples) will be recorded and reported in graph.
However, Trip value, pre-fault and fault value will be recorded and reported. The input channel can
still be used to trig the disturbance recorder.
If
OperationM = Enabled, waveform (samples) will also be recorded and reported in graph.
NomValueM: Nominal value for input M.
OverTrigOpM, UnderTrigOpM: Over or Under trig operation, Disturbance report may trig for
high/low level of analog input M (
Enabled) or not (Disabled).
OverTrigLeM, UnderTrigLeM: Over or under trig level, Trig high/low level relative nominal value for
analog input M in percent of nominal value.
12.7.3.3
Sub-function parameters
M12179-389 v3
All functions are in operation as long as Disturbance report is in operation.
1MRK 505 287-UUS B
Section 12
Monitoring
Busbar protection REB650
203
Application manual
© Copyright 2013 ABB. All rights reserved
Summary of Contents for RELION 650 SERIES
Page 1: ...Relion 650 SERIES Busbar protection REB650 Version 1 3 ANSI Application manual...
Page 2: ......
Page 22: ...16...
Page 34: ...28...
Page 56: ...50...
Page 64: ...58...
Page 76: ...70...
Page 120: ...114...
Page 184: ...178...
Page 216: ...210...
Page 220: ...214...
Page 254: ...248...
Page 261: ...255...