Indications
M12179-448 v4
IndicationMaN: Indication mask for binary input N. If set (Show), a status change of that particular
input, will be fetched and shown in the disturbance summary on local HMI. If not set (
Hide), status
change will not be indicated.
SetLEDN: Set yellow Pick up and red Trip LED on local HMI in front of the IED if binary input N
changes status.
Disturbance recorder
M12179-446 v4
OperationM: Analog channel M is to be recorded by the disturbance recorder (Enabled) or not
(
Disabled).
If
OperationM = Disabled, no waveform (samples) will be recorded and reported in graph.
However, Trip value, pre-fault and fault value will be recorded and reported. The input channel can
still be used to trig the disturbance recorder.
If
OperationM = Enabled, waveform (samples) will also be recorded and reported in graph.
Event recorder
M12179-444 v4
Event recorder function has no dedicated parameters.
Trip value recorder
M12179-442 v3
ZeroAngleRef: The parameter defines which analog signal that will be used as phase angle
reference for all other analog input signals. This signal will also be used for frequency
measurement and the measured frequency is used when calculating trip values. It is suggested to
point out a sampled voltage input signal, for example, a line or busbar phase voltage (channel
1-30).
Sequential of events
M12179-440 v3
function has no dedicated parameters.
12.7.3.4
Consideration
M12179-420 v5
The density of recording equipment in power systems is increasing, since the number of modern
IEDs, where recorders are included, is increasing. This leads to a vast number of recordings at
every single disturbance and a lot of information has to be handled if the recording functions do
not have proper settings. The goal is to optimize the settings in each IED to be able to capture just
valuable disturbances and to maximize the number that is possible to save in the IED.
The recording time should not be longer than necessary (
PostFaultrecT and TimeLimit).
•
Should the function record faults only for the protected object or cover more?
•
How long is the longest expected fault clearing time?
•
Is it necessary to include reclosure in the recording or should a persistent fault generate a
second recording (
PostRetrig)?
Minimize the number of recordings:
•
Binary signals: Use only relevant signals to start the recording that is, protection trip, carrier
receive and/or pickup signals.
•
Analog signals: The level triggering should be used with great care, since unfortunate settings
will cause enormously number of recordings. If nevertheless analog input triggering is used,
chose settings by a sufficient margin from normal operation values. Phase voltages are not
recommended for trigging.
Section 12
1MRK 505 287-UUS B
Monitoring
204
Busbar protection REB650
Application manual
© Copyright 2013 ABB. All rights reserved
Summary of Contents for RELION 650 SERIES
Page 1: ...Relion 650 SERIES Busbar protection REB650 Version 1 3 ANSI Application manual...
Page 2: ......
Page 22: ...16...
Page 34: ...28...
Page 56: ...50...
Page 64: ...58...
Page 76: ...70...
Page 120: ...114...
Page 184: ...178...
Page 216: ...210...
Page 220: ...214...
Page 254: ...248...
Page 261: ...255...